RE-CYCLING TIMER WITH PAUSE

+ Free Shipping

This product is currently out of stock and unavailable.

SKU: N/A Category:

Description

The DT-310/12 provides repetitive forward-reverse cycling for machines
or alternate switching of two loads with a pause between cycles. The
cycle time and the pause time are independently adjustable on a calibrated
scale

Features

  •  Equal repeating forward-reverse cycles
  • Independent adjustment of pause and cycle times.
  • High repetitive accuracy
  • Available in eleven overlapping time ranges from 0.1 seconds to 20 hours
  • Available in various supply voltages from 12VDC to 380VAC

Specification

The unit is ready to operate when power is connected to pins 2 and 10.
On power up the unit starts with the pause, i.e. both contacts on pin 3
and pin 4 are totally isolated from the common pin 1.
When the set pause time has expired the contact between pin 1 and pin 4
will close for a set cycle time.
After expiry of the cycle time has elapsed the contact pin1 and 3 will close for the
set cycle time. After expiry of this cycle time the whole sequence will repeat itself
until the power supply to the unit is disconnected

Operation Controls

  1. Time adjustment for the Pause P1
  2.  led indication for the relay ON
  3. Cycle time adjustment P

TECHNICAL SPECIFICATIONS

Supply Rating Rated for continuous operation input Timing Ranges 0,1 – 2seconds 1 – 20minutes
Protection voltage stabilisation and surge protected 03 – 6seconds 3 – 6minutes
1 – 20 seconds 10 – 200 minutes
AC VOLTAGES 12, 24, 48, 60, 115, 230, 400VAC ± 15% 3 – 60 seconds 30 – 600minutes
40 – 70 Hz, 2.5VA 10 -200 seconds 1 – 2 hours
Overvoltage protection 50% for 1 minute (50Hz) 30 – 600 seconds
DC VOLTAGES 12, 24, 48, 60, 110VDC ± 15% Repetitive Accuracy ± 0.1% ± 5 seconds
Max Ripple 100% (above 50Hz) Overall Accuracy 10%
Consumption 5W/12VDC, 1.5W/24VDC
5W on higher ranges Output 1 x single pole change over relay
Overvoltage protection 100% for 1 minute on 12 and 24 VDC 380VAC – 10A – 2500VA
20% FOR 1 minute on higher ranges Isolation 2500V
Controls Pause duration adjustment P1 General ─20˚C Tto 50˚C
Cycle time adjustment P2 Weight 190gr
Indication Dim LED indicates Time 1 (Pin 4 active)
Bright LED indicates Time 2 (Pin 3 active)

VAC OR VDC

230VAC, 400VAC, 12VDC, 24VDC

SINGLE POLE OR DOUBLE POLE

SP, DP

Shopping Cart