Features
- Interfaces with industrial standard PT-100 temperature sensors.
- Six programmable overlapping temp. ranges between -50 -300°C.
- Programmable for over and under temperature.
- Temperature level adjustment on calibrated scale 0-100%.
- High repetitive accuracy.
- Programmable inversion of relay output for fail-to-safe operation.
- 0 to 1mA proportional output for each temperature range.
- Proportional output is limited to 1,2 mA to protect analogue instruments.
- Latching on under-temperature or 0ver-temperature (programmable).
- 10A SPDT relay output.
Specification
Power Supply
AC: Supply Voltage: 12,24,115,230,400,415,525V ±15%
Isolation (sensor input to power supply): 2kV
Power Consumption: 3VA, 6VA for 415, 525V (approx)
DC: Supply Voltage: 12, 24V 15%
Isolation: No galvanic isolation
Power Consumption: 100mA
Connection Cable
2 – core, unscreened. Resistance of long cables affect temp. accuracy (approx. 1ºC per 0.3 ohms)
Sensor Input
Type PT-100 resistive temperature sensor.
Short-circuit current: 1mA
Open-circuit voltage: 220mV
Temperature Sensing Range
Repetitive accuracy : 1%