CURRENT WINDOW COMPARATOR – SINGLE PHASE

+ Free Shipping

This product is currently out of stock and unavailable.

SKU: N/A Category:

Features: 

  • Direct in-line current sensing
  • Combined overload and underload detection
  • Internal shunt for direct line-in current sensing
  • Adjustable responsible delay of 0.1 to 10 seconds on SP123
  • 1A or 5A AC input range (programmable)
  • Direct interface with conventional current transformers
  • Separate adjustable of overload and underload threshold
  • Lathing in both modes
  • LED indications for overload, underload and normal load
  • Start-up delay
  • 10A SPDT relay output

Specifications:

AC: Supply voltage : 12, 24, 115, 230, 400, 415, 525V ±15% Isolation (current input to power supply): 2kV

Power consumption: 3VA (approx), 6VA for 415, 525V(approx)

DC: Supply voltage: 10-30V, 48, 60, 110V ±15%

Isolation: No galvanic isolation.

Power Consumption: 100mA (10-30V), 30mA for 48V and higher.

Current input: 

Trip point: 0.1 to 1A or 0.5 to 5A AC (adjustable)

Repetitive accuracy: 1%

Hysteresis: 2% Fixed (relative to the trip point setting)

Maximum input current (continuous): 6A

Peak short-term over-current (10 seconds): 20A

Current input impedance: 50milliohms

Response:

Start-up delay: approximately 10 seconds, standard (1 to 15 seconds also possible on special order)

Response delay: 

SP120 – 1 second

SP123 – adjustable from 1 to 10 seconds (other ranges on special order)

VAC OR VDC

24VAC, 30VDC, 48VAC, 110VDC, 115VAC, 125VDC, 230VAC, 400VAC, 440VAC, 415VAC, 525VAC

DP OR SP

DP, SP

Shopping Cart